ES710/5KVA,ES710/5000,ES710-5KVA,ES710-5000
      ES710/3150/4000/5000/6300/8000/10000提供ES710-3.15KVA隔離變壓器、ES710-4KVA隔離變壓器、ES710-5KVA隔離變壓器、ES710-6.3KVA隔離變壓器、ES710-8KVA隔離變壓器、ES710-10KVA隔離變壓器、ES710/3150隔離變壓器、ES710/4000隔離變壓器、ES710/5000隔離變壓器、ES710/6300隔離變壓器、ES710/8000隔離變壓器、ES710/10000隔離變壓器 ES710醫用隔離變壓器ES710/3150,ES710-3150,ES710-3.15,ES710-3KVA,ES710-4000,ES710/4000,ES710-4KVA,ES710/4KVA,ES710-5000,ES710/5000,ES710-5KVA,ES710/5KVA,ES710-6KVA,ES710-6000,ES710/6000,ES710-7KVA,ES710/6.3KVA,ES710-6300,ES710/6300,ES710-7KVA,ES710/7KVA,ES710-8KVA,ES710/8000,ES710/8KVA,ES710/10000,ES710-10KVA,ES710/10KVA,ES710/8KVA,ES710/8000,ES710-8KVA,ES710/6300,ES710-6.3KVA,,ES710/6.3KVA,ES710-6300,ES710/3150,ES710-3150,ES710-3.15,ES710-3KVA,ES710-4000,ES710/4000,ES710-4KVA,ES710/4KVA,ES710-5000,ES710/5000,ES710-5KVA,ES710/5KVA,ES710/8KVA,ES710/8000,ES710-8KVA,ES710/6300,ES710-6.3KVA,ES710/6.3KVA,ES710-6300,ES710/3150,ES710-3150,ES710-3.15,ES710-3KVA,ES710-4000ES710/4000,ES710-4KVA,ES710/4KVA,ES710-5000ES710/5000,ES710-5KVA,ES710/5KVAES710-3.15KVA隔離變壓器、ES710-4KVA隔離變壓器、ES710-5KVA隔離變壓器、ES710-6.3KVA隔離變壓器、ES710-8KVA隔離變壓器、ES710-10KVA隔離變壓器、ES710/3150隔離變壓器、ES710/4000隔離變壓器、ES710/5000隔離變壓器、ES710/6300隔離變壓器、ES710/8000隔離變壓器、ES710/10000隔離變壓器為醫療建筑物2類場所醫用變壓器.
手術室,重癥監護室ICU CCU等特殊場合使用的醫用隔離電源系統須含有以下系統
1每間I級手術間按原設計配電思路以及總負荷配備不應小于10KVA,且必須設置≥6.3KVA隔離變壓器構成的IT系統(包括隔離變壓器、絕緣監測儀、電流互感器、儀器專用電源、外接報警顯示和測試單元); 每間Ⅲ級手術室總配電負荷不應小于8KVA,IT系統≥6.3KVA隔離變壓器構成的;IT系統最大分斷時間230V應為0.2S.
2醫用隔離電源系統由醫用隔離變壓器,絕緣監測,外接報警裝置,斷路器等主要元件組成,并符合以下標準:
3 滿足《建筑物電氣裝置第7-710部分:特殊裝置或場所得要求—醫療場所》GB16895.24-2005 / IEC60364-7-710:2002 710.512.1.6中規定:醫用隔離變壓器應符合IEC61558-2-15的要求。
4 變壓器的二次側額定電壓Un不應超過250V,用于移動式和固定式設備的醫療IT系統應采用單相變壓器,其額定輸出容量不應小于0.5KVA,但不應超過10KVA。
5 醫用隔離變壓器的金屬外殼需與局部等電位聯結端子板聯結。
6絕緣監測儀
7絕緣監視報警系統符合IEC61557-8和IEC60364-7-710標準。
8交流內阻抗應至少為100kΩ;測試電壓不應大于直流25V;即使在故障情況下,其注入電流的峰值不應大于1Ma;最遲在絕緣電阻降至50 kΩ時,應發出信號。應配置試驗此功能的器具。
9報警顯示系統 
醫用隔離電源 醫用隔離變壓器醫用絕緣監視儀 漏電監測儀(剩余電流監視儀)漏電監視儀系統(剩余電流監視儀系統)
如您有這塊的需要,歡迎來電咨詢與洽談。