一.Main characteristics
1.Meets all the requirement of field tests. This tester with standard 6
phase voltage, 6 phase current output, voltage 125V/phase, current
30A/phase, 6 phases in parallel can up to 180A. Digital Signal Processor
Microcomputer. Not only test the traditional relays and protectors, but
also test the modern micro computer relays, special for transformer
differential protection and transfer equipments
2.All technical indicators fully meet the standard DL/T624-1997:
Technical condition of the relay computer test device.
3.Classic Windows XP operating interface, friendly man-machine
interface, easy and fast to operate High-performance embedded
industrial control computer and 8.4 inch resolution of 800 × 600 TFT
true color display which provides rich visual information, includes the
current working condition and all kinds of help information.
4.The Windows XP system comes with the restore function avoid system
crashes caused due to illegal shutdown, or malfunction, etc.
5.Equipped with ultra-thin industrial keyboard and optical mouse,
complete a variety of operations using keyboard or mouse the same as
ordinary PC.
6.The main control board is DSP + FPGA architecture, 16 bit DAC output,
generates high - density sine wave 2000 points each circle to
fundamental wave, which greatly improve the wave quality and the
accuracy of the test instrument.
7.Using high-fidelity linear amplifier. Both to ensure the accuracy of a
low current, but also guarantee the stability of the high current.
8.USB directly connect with PC, without any adapter cable, easy to use.
9.Can be connected to a laptop computer (optional).Laptop computers and
industrial machines use the same software, no need to re-learn the
methods of operation.
10.With a separate DC auxiliary voltage source, output voltage 110V(1A)
,220V(0.6A), provides relays or protective devices which require DC
power.
11.The software with self calibrating function, which avoid to calibrate
accuracy by adjusting relays after open the case, greatly improve the
stability of the accuracy.
二. Technique parameters   
1.AC current source
Current range: 6x (0~30A)/phase, accuracy 0.2%.   
6 phase parallel current output: 180A
Phase current working value for allowed long time: 10A
Power: 300VA/phase
Maximum output power of 6 phases in parallel: 900VA
Maximum permitted work time of 6 phases in parallel: 10S
Frequency range: 0~1000Hz accuracy: 0.001Hz
Harmonic time: 2~20 phase: 0——360° accuracy: 0.1°
2.DC current source
Current range: 20A / phase, power: 300VA/phase, accuracy:0.2%
3.AC voltage source
Phase voltage output:6x( 0~125V)/phase, accuracy: 0.2%   
Line voltage output: 0~250V
Phase voltage / Line voltage output power: 70VA / 100VA
Frequency range: 0~1000Hz accuracy: 0.001Hz
Harmonic time: 2~20 phase: 0——360° accuracy: 0.1°
4.DC voltage source
Phase voltage output range: 0~±150V  accuracy: 0.2%
Line voltage output range: 0~±300V
Phase voltage / Line voltage output power: 90VA / 180VA
5.Switch terminal
Switch input terminals: 8 pairs
Dead contact: 1-20mA, 24V active output inside the device.
Potential flip: 0——6V DC low level
                      15-250V DC high level
Switch output terminals: 4 pairs, dead contact, rupturing ca